Specifications |
|
Input data |
|
|
Inputs |
P 43000 D2 |
±1 A, ±1.5 A, ±2 A, ±3 A, ±5 A, |
Calibrated range selection, default: ±5A |
|
|
P 43000 D2-nnnn |
0.1 A ... 5 A, uni/bipolar |
1 to 16 ranges to customer requirements, |
|
|
|
calibrated range selection |
|
P 43100 D2-nnnn |
0.1 A ... 5 A, uni/bipolar |
Fixed setting to customer requirements |
|
|
Input resistance |
<0.6 ohms |
|
|
Input capacitance |
Approx. 1 nF |
|
|
Overload |
20 % full scale |
|
Output data |
|
|
Output |
P 43000 D2 |
20 mA, 10 V uni/bipolar |
Calibrated range selection, default: ±10 V |
|
|
and 4 ... 20 mA |
|
P 43000 D2-nnnn |
20 mA, 10 V uni/bipolar |
Calibrated range selection, to customer |
|
|
and/or 4 ... 20 mA |
requirements |
|
P 43100 D2-nnnn |
20 mA, 10 V uni/bipolar |
Fixed setting to customer requirements |
|
|
or 4 ... 20 mA |
|
|
Offset |
Factory setting up to ±150 % |
|
|
Load |
With output current |
≤12 V (600 ohms at 20 mA) |
|
With output voltage |
≤10 mA (1000 ohms at 10 V) |
|
|
Offset error |
20 µA or 10 mV |
|
|
Residual ripple |
<10 mVrms |
|
Transmission behavior |
|
|
Gain error |
<0.3 % meas. val. |
|
|
Cut-off frequency |
Approx. 5 kHz; optional factory setting: 10 Hz |
(–3 dB) |
|
|
Common mode |
CMRR1) |
DC: approx. 160 dB |
rejection ratio |
|
AC 50 Hz:approx. 100 dB |
|
|
Temperature |
<0.005 %/K meas. val. |
influence 2) |
|
Power supply |
|
|
Power supply |
20 ... 253 V AC/DC |
AC 48 ... 62 Hz, approx. 2 VA; max. approx. 1.2 W |
|
Isolation |
|
|
Galvanic isolation |
3-port isolation between input, output, and power supply |
|
|
Test voltage |
Calibrated range |
10 kV AC across input and output/power supply |
|
selection |
|
Fixed settings |
15 kV AC across input and output/power supply |
|
(Type P43100D2-nnnn) |
|
All models |
4 kV AC output to power supply |
|
|
Working voltage |
Calibrated range |
Up to 2200 V AC/DC across input, output, and power supply with overvoltage |
(basic insulation) |
selection |
category III and pollution degree 2 (transient overvoltage: 13.5 kV) |
EN 61010-1 |
Fixed settings |
Up to 3600 V AC/DC across input, output, power supply with overvoltage category III |
|
(Type P43100D2-nnnn) |
and pollution degree 2 (transient overvoltage: 20 kV) |
|
|
Rated insulation |
Calibrated range |
Up to 2200 V AC/DC across input, output, and power supply with overvoltage |
voltage to |
selection |
category III and pollution degree 2 |
EN 50124-1 |
Fixed settings |
Up to 3000 V AC/DC across input, output, and power supply with overvoltage |
|
(Type P43100D2-nnnn) |
category III and pollution degree 2 |
|
|
Protection against |
Calibrated range |
Protective separation to EN 61140 by reinforced insulation according to EN 61010-1 |
electric shock |
selection |
Working voltages with overvoltage category III and pollution degree 2: |
|
|
– up to 1100 V AC/DC across input and output/power supply |
|
|
– up to 300 V AC/DC across output and power supply |
|
Fixed settings |
Protective separation to EN 61140 by reinforced insulation according to EN 61010-1 |
|
(Type P43100D2-nnnn) |
Working voltages with overvoltage category III and pollution degree 2: |
|
|
– up to 1100 V AC/DC across input and output/power supply |
|
|
– up to 300 V AC/DC across output and power supply |
|
For applications with high working voltages, you should ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks. |
Standards and approvals |
|
|
EMC3) |
Product standard EN 61326 |
|
Emitted interference: |
Class B |
|
Immunity to interference: |
Industry |
|
|
Surge withstand |
5 kV, 1.2/50 µs, to IEC 255-4 (higher values upon request) |
|
Further data |
|
|
MTBF4) |
approx. 96 years |
|
|
Ambient temperature5) |
Operation: |
–10 ... +70 °C |
|
Transport and storage: |
–40 ... +85 °C |
|
|
Design |
Modular housing |
45.0 mm |
|
with screw |
See dimension drawing for other measurements |
|
connectors |
|
|
Protection class |
Housing IP 40, terminals IP 20 |
|
|
Mounting |
Snap-on mounting on 35-mm top-hat rail according to EN 60715 |
|
|
Weight |
Approx. 350 g |
|
|
1) Common-Mode Rejection Ratio = |
2) Reference temperature for TC specifications = 23 °C, the average TC is specified |
3) Slight deviations are possible during interference |
4) Mean Time Between Failures - MTBF - to EN 61709 (SN 29500). Conditions: stationary operation in well-tended rooms, average ambient temperature 40 °C, no ventilation, permanent operation |
5) Extended temperature range –25 ... +85 °C on request |
|