Specifications |
|
Input data |
|
|
Inputs |
0 ... 20 mA |
|
4 ... 20 mA |
|
0 ... 10 V |
switchable (factory setting 0 ... 20 mA) |
|
|
Input resistance |
Current input: |
Voltage drop < 0.1 V at 20 mA |
|
Voltage input: |
Approx. 100 kohms |
|
|
Overload capacity |
Current input: |
<100 mA |
|
Voltage input: |
Voltage limited to 30 V by suppressor diode, |
|
|
max. permissible continuous current: 3 mA |
|
Output data |
|
|
Outputs |
0 ... 20 mA |
|
4 ... 20 mA |
|
0 ... 10 V |
switchable (factory setting 0 ... 20 mA) |
|
|
Load |
With output current: |
≤ 10 V (≤ 500 ohms at 20 mA) |
|
With output voltage: |
≤1 mA (≥ 10 kohms at 10 V) |
|
|
Offset |
< 20 µA or < 10 mV |
|
|
Residual ripple |
<10 mVrms |
|
Transmission behavior |
|
|
Gain error |
< 0.2 % of measured value with direct 1:1 current transmission |
|
< 0.3 % of measured value with voltage input and/or voltage output |
|
Additional error in live-zero operation 20 µA or 10 mV |
|
|
Temp influence |
< 0.01 %/K full scale (reference temp. 23 °C) |
|
Average TC in specified operating temperature range 0 ... +55 °C |
|
|
Cutoff frequency |
>100 Hz, –3 dB |
|
Power supply |
|
|
Power supply |
24 V ... 110 V DC (±25%), approx. 1.0 W |
|
110 V ... 230 V AC (± 10%), approx. 2.0 VA |
|
|
Isolation |
|
|
Test voltage |
2.5 kV AC, 50 Hz |
|
|
|
Working voltage |
Up to 300 V AC/DC across input and output / power supply, for overvoltage category II |
(basic insulation) |
and pollution degree 2, up to 100 V AC/DC across output and |
|
power supply for category II and degree 2 according to EN 61010 Part 1. |
|
|
Protection against |
Protective separation according to EN 61140 by reinforced insulation according to EN 61010 |
electric shock |
Part 1 up to 300 V with overvoltage category II and pollution degree 2 across |
|
input and output/power supply. |
|
For applications with high working voltages, you should ensure there is sufficient spacing or |
|
isolation from neighboring devices and protection against electric shocks. |
|
Standards and approvals |
|
|
EMC |
Product family standard: |
EN 61326 |
|
Emitted interference: |
Class B |
|
Immunity to interference: |
Industry |
|
Slight deviations are possible during interference |
|
|
Approval |
cULus Listed, |
(pending) |
Standard: UL 61010-1 and CSA C22.2 No. 61010-1 |
|
Other data |
|
|
MTBF |
Approx. 280 years |
|
Mean Time Between Failures – MTBF – according to EN 61709 (SN 29500) |
|
Conditions: stationary operation in well-kept rooms, |
|
average ambient temperature 40 ºC, no ventilation, continuous operation |
|
|
|
Ambient temperature |
during operation: |
0 ... +55 ºC |
|
during storage: |
–40 ... +85 ºC |
|
|
Design |
Modular housing with screw terminals, width 6.1 mm |
|
see dimension drawings for further dimensions |
|
|
Ingress protection |
IP 20 |
|
|
Mounting |
For 35-mm top-hat rail (EN 60715) |
|
|
Weight |
Approx. 50 g |